FRP Counterflow Cooling Towers
Induced draft FRP counterflow cooling towers in square and rectangular modules, factory-built for fast installation and high thermal efficiency in a compact footprint.
See specificationsIn a forced draft cooling tower the fan sits at the air inlet near the base and pushes air up through the fill. Mechanical equipment stays out of the warm, wet exhaust air, is easy to reach for maintenance, and the tower can work against duct static pressure for indoor or enclosed locations. We design forced draft towers to your duty with axial or centrifugal fans as the site requires.
Fans and motors at ground level sit in dry inlet air, simplifying inspection and extending equipment life.
Centrifugal fan options handle duct static pressure, allowing towers to be placed inside buildings or plant rooms.
Fans in the dry inlet stream are less exposed to icing, useful for sites with cold winters.
FRP or galvanised steel casing with stainless fasteners for long, low-maintenance service.
Lower power option for outdoor installations with free air inlet.
Quieter operation and the ability to work against duct pressure for indoor or screened sites.
Forced draft arrangement combined with a coil for closed circuit duties.
| Configuration | Forced draft, counterflow |
|---|---|
| Capacity | Designed to your duty |
| Fan type | Axial or centrifugal, base-mounted |
| External static | Ducted designs on request |
| Fill type | PVC film fill |
| Casing | FRP or hot-dip galvanised steel |
Forced draft towers push air in at the base, while induced draft towers pull air out at the top. Forced draft keeps mechanical equipment dry and accessible and can handle ducting; induced draft usually offers lower fan power and less risk of warm air recirculation.
Because exhaust velocity is lower, layout matters. We review your site arrangement and recommend spacing or discharge hoods to minimise recirculation.
Circulating water flow, hot and cold water temperatures, design wet-bulb temperature at site, available plot area, water quality and power supply details. If some data is missing, our design team can help you establish it from your process and local climate data.
Yes. We supply cooling towers, spares and service to clients across the Middle East, Africa, Asia, Europe and the Americas. Towers are designed for the site climate, broken down into container-friendly modules where possible, export-packed and shipped to any port worldwide with erection drawings and documentation.
Yes. Third-party and client inspection is welcome at our factories in Coimbatore, including material checks, dimensional inspection, fan balancing records and pre-dispatch inspection, as agreed in the inspection and test plan.
We provide erection drawings and manuals with every supply, and our engineers can supervise erection and commissioning in India and overseas on request, or support your local contractor remotely.

Induced draft FRP counterflow cooling towers in square and rectangular modules, factory-built for fast installation and high thermal efficiency in a compact footprint.
See specifications
FRP crossflow cooling towers with gravity hot-water basins, low pumping head and easy access to fill and distribution for routine maintenance.
See specifications
Compact round bottle-shaped FRP cooling towers for smaller loads, with a rotating sprinkler, light weight and quick installation.
See specificationsGive us the date your equipment must be on site. We will plan design, fabrication, inspection and shipping backwards from it and tell you honestly if it is achievable.